ETRI-Knowledge Sharing Plaform

KOREAN
논문 검색
Type SCI
Year ~ Keyword

Detail

Conference Paper CES Peak Demand Shaving with Energy Storage System
Cited 7 time in scopus Share share facebook twitter linkedin kakaostory
Authors
Soyoung Park, Wan-Ki PARK
Issue Date
2017-10
Citation
International Conference on Information and Communication Technology Convergence (ICTC) 2017, pp.1125-1127
Publisher
IEEE
Language
English
Type
Conference Paper
DOI
https://dx.doi.org/10.1109/ICTC.2017.8190874
Abstract
This paper analyzes energy cost reduction from peak demand shaving when a CES provider adopts ESS for the CHP-based CES microgrid site in Seoul, Korea. The simulation results show that about 9% of peak shaving can be realized when a 270kWh ESS is used for three thousand CES households. When two or three ESSs are adopted, peak demand shaving increases at most into 12% or 14%, which concludes that ESS capacity enlargement is not so helpful for the peak reduction. It also concludes that peak shaving is appropriate as a supplementary usage of ESS considering that ESS is required to work only a few days for a year to achieve peak shaving.
KSP Keywords
Energy cost reduction, Peak Shaving, energy storage system, peak demand, peak reduction, simulation results